Smart Range

Enter the last inspection date — get the annual, semi-annual and quarterly windows

Last completed inspection

Type it, paste it, or pick from the calendar.

Windows use ±30/20/10 days (annual / semi / quarterly) — the usual TJC survey expectation.

CSVCalendar (.ics)
Enter the last inspection date above — the annual, semi-annual and quarterly windows appear here.
Advanced optionsNFPA 25 windows · specific ITM task · tolerances · horizon · calendar
Compare against the standard
Specific ITM task

Optional. Adds that task’s own frequency as an extra card when it isn’t already one of the three.

Tolerances & horizon
Calendar
Where these numbers come from

The ±30/20/10 day default is TJC survey practice (EC.02.03.05 / CAMH) — what an accreditation surveyor expects. It is not in NFPA 25 and not a CMS regulation. NFPA 25 §3.7.1.4–8 instead defines frequency as a month range (annual 9–15, semiannual 4–8, quarterly 2–4, 3-year 30–40, 5-year 54–66), which the checkbox above will show alongside. NFPA 72 defines no min/max variation in any edition, so fire alarm work follows the calendar frequency plus whatever your surveyor or AHJ expects. Task frequencies and section numbers come from our NFPA 25 summary table. Planning aid only — your AHJ’s adopted edition governs, and CMS still enforces older editions in certified healthcare occupancies.