Skip to main content
🧰 SAMEKTRA SERVICES →
HOMETOOLS

NFPA 25 ITM Frequency Table

Filter and sort common inspection, testing, and maintenance requirements for water-based fire protection systems

Disclaimer: Summarized in our own words. Always verify against your adopted edition of NFPA 25 and AHJ requirements. This is a quick reference only — not a substitute for the standard.
SYSTEM TYPE
FREQUENCY
COMPONENT
TASK
Showing 71 of 71 items · click a header to sort
ComponentItemTaskFrequency ▲SectionNotes
Sprinkler
DryPreactionDeluge
Gauges (dry, preaction, deluge)InspectionWeekly5.2.4.1Verify normal air and water pressure and condition
Sprinkler
Dry
Air pressure (dry system)InspectionWeekly13.4.4.1.1Verify normal air pressure on supply and system gauges
Valves
All Systems
Control valves (sealed)InspectionWeekly13.3.2.1Verify in correct position and sealed
Fire Pump
Fire Pump
Pump house / pump room conditionsInspectionWeekly8.2.2Heat ≥ 40°F (4°C) for diesel; ventilation, louvers, lighting; no leaks; gauge readings normal
Fire Pump
Fire Pump
Diesel engine fuel level and batteryInspectionWeekly8.2.2(3)Fuel ≥ 2/3 tank; batteries charged; no leaks
Fire Pump
Fire Pump
Pump packing gland leakageInspectionWeekly8.2.2(2)(g)Approximately one drop per second from each packing gland; adjust if higher
Fire Pump
Fire Pump
Diesel pump no-flow (churn) testTestWeekly8.3.1.1Run at least 30 minutes each week
Water Tank
Water Storage
Tank water temperature (cold climate)InspectionWeekly9.2.4Verify water temperature ≥ 40°F (4°C) during freezing weather
Sprinkler
Wet
Gauges (wet pipe)InspectionMonthly5.2.4.2Verify good condition and normal water pressure is maintained
Sprinkler
Dry
Air compressor and pressure maintenance deviceInspectionMonthly13.4.4.1.1Verify operation and ability to restore pressure within 30 minutes
Valves
All Systems
Control valves (locked or supervised)InspectionMonthly13.3.2.1Verify in correct position; locked or electrically supervised
Fire Pump
Fire Pump
Electric pump no-flow (churn) testTestMonthly8.3.1.1Run at least 10 minutes; monitor for cavitation, overheating, pressure
Water Tank
Water Storage
Tank condition (water level, heating, catwalks)InspectionMonthly9.2.1More frequent where freezing is a concern
Sprinkler
Dry
Priming water level (dry pipe valve)TestQuarterly13.4.4.1.2.1Check the priming water level via the priming water test cock
Sprinkler
Dry
Auxiliary drains / drum dripsInspectionQuarterly13.4.4.3.2Inspect for accumulated water; drain as needed
Sprinkler
Dry
Quick-opening device (accelerator / exhauster)InspectionQuarterly13.4.4.1.4Inspect to verify it is in service and the control valve is open
Sprinkler
Preaction
Preaction valve trim and enclosureInspectionQuarterly13.4.3.1.1Inspect trim, priming water, and enclosure heat
Sprinkler
Deluge
Deluge valve trim and enclosureInspectionQuarterly13.4.3.1.1Inspect trim, pilot lines, and enclosure heat
Valves
All Systems
Pressure-reducing valve (sprinkler) — partial flowTestQuarterly13.5.1.2Verify pressures and that valve is operating
Sprinkler
All Systems
Waterflow alarm devicesTestQuarterly5.3.3Open inspector's test connection at the most hydraulically remote point
Sprinkler
All Systems
Supervisory signal devices (except valve)TestQuarterly13.3.3.5Verify signal transmission and device operation
Standpipe
Standpipe
Hose connections, caps, and gasketsInspectionQuarterly6.2.1Verify accessibility, condition, and identification
Standpipe
Standpipe
Hose valvesInspectionQuarterly6.2.3Accessible, handwheel in place, not obstructed
Standpipe
Standpipe
Hose storage cabinets and Class II hose stationsInspectionQuarterly6.2.1.5Verify hose, nozzles, and cabinet condition
FDC
All Systems
Fire Department Connection — visual inspectionInspectionQuarterly13.7.1Visible, accessible, couplings/swivels OK, plugs/caps in place, gaskets intact, identification sign present, check valve not leaking, drain (clapper) functional, interior free of obstructions
Water Tank
Water Storage
Tank water level signal deviceTestQuarterly9.3.4Verify high and low water level alarm operation
Sprinkler
Preaction
Detection devices (smoke/heat) — preactionTestSemiannual13.4.3.2.4Per NFPA 72; coordinate with detection ITM program
Valves
All Systems
Valve supervisory (tamper) switchesTestSemiannual13.3.3.5Verify signal within first two revolutions or before valve travels 1/5 from normal position
Sprinkler
All Systems
Sprinklers and piping (floor-level inspection)InspectionAnnual5.2.1Inspect from floor for leaks, corrosion, paint, obstruction, misalignment, loading
Sprinkler
All Systems
Pipe hangers and seismic bracingInspectionAnnual5.2.3Inspect after any seismic event for damage or missing components
Sprinkler
All Systems
Spare sprinkler cabinet stockInspectionAnnual5.2.1.3Verify minimum spare count, all types present, listed wrench
Sprinkler
Wet
Antifreeze solutionTestAnnual5.3.4Before onset of freezing weather; replace premix when required
Sprinkler
Dry
Auxiliary drains / drum drips — drainMaintenanceAnnual13.4.4.3Drain before onset of freezing weather and after each trip test
Sprinkler
Dry
Quick-opening device (QOD) operation testTestAnnual13.4.4.1.4.2Tested at the same interval as the dry pipe valve trip test
Sprinkler
Dry
Dry pipe valve trip test (partial flow)TestAnnual13.4.4.2.2Warm weather; measure trip time from inspector's test connection
Sprinkler
Dry
Dry pipe valve internal inspectionInspectionAnnual13.4.4.2.1Performed in conjunction with annual trip test
Sprinkler
Dry
Low-point drains (dry systems)MaintenanceAnnual13.4.4.3Drain before onset of freezing weather
Sprinkler
Preaction
Preaction valve internal inspectionInspectionAnnual13.4.3.1.2Performed during annual trip test
Sprinkler
Preaction
Preaction valve trip testTestAnnual13.4.3.2Trip the detection circuit and verify valve operation
Sprinkler
Deluge
Deluge valve internal inspectionInspectionAnnual13.4.3.1.2Performed during annual trip test
Sprinkler
Deluge
Deluge valve trip testTestAnnual13.4.3.2Trip the release and verify all open nozzles flow
Sprinkler
Deluge
Open nozzles (deluge)InspectionAnnual5.2.1.2Inspect each open nozzle for damage, corrosion, and obstruction
Valves
All Systems
PIV (post indicator valve) operationMaintenanceAnnual13.3.3.1Operate through full range and return to normal position
Valves
All Systems
Backflow preventer forward flow testTestAnnual13.6.2.1Flow at system demand; RPZ also requires annual internal inspection
Sprinkler
All Systems
Main drain test (at each riser)TestAnnual13.2.5Verify water supply condition; compare to baseline
Standpipe
Standpipe
Pressure-regulating devices (partial flow)TestAnnual6.3.2.1Verify proper static and residual pressures annually
Fire Pump
Fire Pump
Annual fire pump flow testTestAnnual8.3.3Minimum 0%, 100%, 150% of rated flow; compare to acceptance curve
Fire Pump
Fire Pump
Suction screen / strainer cleaningMaintenanceAnnual8.3.3.5After each annual flow test or after any obstruction event
Fire Pump
Fire Pump
Transfer switch (ATS) testTestAnnual8.3.2.7Coincide with annual pump flow test; verify transfer in both directions
Fire Pump
Fire Pump
Diesel engine batteries — load test / replacementMaintenanceAnnual8.5 TableReplace at manufacturer interval; load test annually
Water Tank
Water Storage
Tank exterior painted surfacesMaintenanceAnnual9.2.5Inspect and recoat as needed to prevent corrosion
Private Hydrant
All Systems
Hydrant inspectionInspectionAnnual7.2.2.4After each operation and at least annually
Private Hydrant
All Systems
Hydrant flow test and lubricationMaintenanceAnnual7.3.2Operate through full range, lubricate, flush
Sprinkler
Dry
Dry pipe valve full-flow trip testTest3-Year13.4.4.2.2.1Full-flow with control valve fully open
Sprinkler
Dry
Air leak rate / pneumatic testTest3-Year13.4.4.2.6System shall not lose more than 1.5 psi in 2 hours
Sprinkler
Preaction
Preaction valve full-flow trip testTest3-Year13.4.3.2.2Full-flow with control valve fully open
Sprinkler
Deluge
Deluge valve full-flow trip testTest3-Year13.4.3.2.2Full-flow with control valve fully open
Water Tank
Water Storage
Tank interior (drained inspection)Inspection3-Year9.2.6Every 5 years for tanks without cathodic protection; every 3 years for steel without corrosion protection
Sprinkler
All Systems
Dry sidewall and extra-high-temp sprinkler sample testTest5-Year5.3.1.1More frequent sampling than standard-response heads
Sprinkler
Wet
Alarm check valve — internal inspectionInspection5-Year13.4.1.2Internal parts clean, moving freely, no obstruction
Sprinkler
Wet
Alarm check valve — strainers/filters/restricted orificesMaintenance5-Year13.4.1.3Internal cleaning at the same interval as the valve
Valves
All Systems
Check valve internal inspectionInspection5-Year13.4.2.1Internal parts clean, moving freely, in good condition
Valves
All Systems
Pressure-reducing valve (sprinkler) — full flowTest5-Year13.5.1.2.1Full-flow performance test
Standpipe
Standpipe
Standpipe flow testTest5-Year6.3.1Verify required flow and pressure at hydraulically remote connection
Standpipe
Standpipe
Pressure-regulating devices (full flow)Test5-Year6.3.2Verify outlet pressure; recalibrate or replace as needed
Standpipe
Standpipe
Hydrostatic test (dry, semi-auto, manual)Test5-Year6.3.3200 psi for 2 hours, or 50 psi above maximum pressure
Standpipe
Standpipe
Class II occupant-use hose service testTest5-Year6.3.5Hydrostatic test of fire hose per NFPA 1962
FDC
All Systems
FDC internal inspection (after testing)Inspection5-Year13.7.2Hose threads checked; clapper inspected; piping back-flushed if needed
Water Supply
All Systems
Private fire service main flow testTest5-Year7.3.1Flow at hydrant or other approved outlet
Sprinkler
All Systems
Fast-response sprinkler sample testTest20-Year5.3.1.1Test or replace at 20 years, then every 10 years
Sprinkler
All Systems
Standard-response sprinkler sample testTest50-Year5.3.1.1Test or replace at 50 years, then every 10 years
Browse the full NFPA 25 section reference →