High-Flow Fire Extinguishers
The 1 lb/sec rule: what it is, where NFPA 10 requires it, and why it is coming to every gas station

A bigger extinguisher is not a faster one. NFPA 10 asks for at least 10 lb of dry chemical discharged at 1 lb per second or more on pressure, three-dimensional and obstacle fires, and NFPA 30A now asks for the same at fuel dispensers. Here is what the rule says, how to read a data sheet for it, and what to change on your next service visit.

By LifeSafetyWiki · 11 min read · Last updated November 6, 2026
Headshot of Mike McCarthy, owner of FirePro Inc.
CONTRIBUTOR · FIELD EXPERTISE

Mike McCarthy

Owner of FirePro Inc. in Lawrenceville, Georgia — a portable fire extinguisher and emergency lighting company that has served commercial clients across Gwinnett, Cherokee, Fulton, DeKalb and Forsyth counties since the 1990s. Mike raised the topic of this article: high-flow extinguishers are becoming mandatory at every gas station and fuel island.

The biggest extinguisher on the wall can be the wrong one

Picture a pump seal letting go in a fuel room. Diesel sprays out at pressure, lights, and the nearest employee grabs the biggest extinguisher in sight: a 30 lb unit with a 160-B rating on the label. It is a good extinguisher. It is also the wrong one. On its manufacturer’s data sheet it averages 0.95 lb of powder a second, and a spray fire is fed faster than that. The flame takes the powder, comes back, and the cylinder is empty in about half a minute.

A 10 lb unit with a 20-B rating on the same shelf would have discharged at 1.22 lb a second. Smaller cylinder, smaller rating, more powder in the first seconds, which is the only time that matters on a pressure fire. That gap is what NFPA 10 means when it asks for a high-flow extinguisher, and since the 2021 edition of NFPA 30A it is what every fuel dispenser in the country is supposed to have next to it.

AVERAGE DISCHARGE RATE, LB/SEC0.00.51.0Amerex 720 · 10 lb ABC · High Flow1-A:20-B:C1.22Ansul Sentry HF-AA10S · 10 lb ABC1-A:20-B:C1.26Buckeye 11351 · 10 lb ABC · HD High Flow1-A:20-B:C1.11Amerex 760 · 20 lb ABC · High Flow4-A:60-B:C1.14Amerex 581 · 20 lb ABC · Fast Flow4-A:40-B:C1.20Amerex 594 · 13.2 lb ABC · Fast Flow2-A:40-B:C0.94Amerex 589 · 30 lb ABC · Compliance Flow20-A:160-B:C0.95Amerex 564 · 20 lb ABC · Compliance Flow20-A:120-B:C0.651 lb/sec line
Average discharge rates as printed on Amerex’s High Flow and High Performance data sheets, Ansul’s Sentry High-Flow listing and Buckeye’s Heavy Duty High Flow spec sheet (manufacturer figures, not NFPA tests). The highest-rated unit on the chart, a 30 lb 20-A:160-B:C, is under the line. So is a 13.2 lb model sold as “Fast Flow.”

What NFPA 10 actually requires

NFPA 10 never says “high flow.” It sets a size and a rate for three Class B hazards in Section 5.5, Selection for Specific Hazards. Section numbers below are the 2018 edition, read in our copy; the crosswalk further down gives the 2013 and 2026 numbers.

Pressurized flammable liquids and gas — 5.5.1.1

Fuel that is forced, pumped or sprayed (the 3.3.23 definition): a leaking flange on a fuel line, a failed hydraulic hose, a propane fitting. Required: dry chemical, 10 lb or more, discharging at 1 lb/sec (0.45 kg/sec) or more. Annex A.5.5.1.1 explains why: agents other than dry chemical are relatively ineffective here, and the Class B rating test does not apply.

Three-dimensional fires — 5.5.2

Fuel that is pouring, running or dripping, burning on a vertical surface as well as on the floor: a punctured drum on a rack, oil running down an engine block. Same requirement: dry chemical, 10 lb or more, 1 lb/sec or more. Annex C.2.6.4 adds the technique: start at the bottom and work up, and do not count on foam, because the fuel is moving.

Obstacle fires — 5.5.3

Fuel burning all around a sizable object, such as a tank, a mixer or a vehicle, so one person on one side has a blind spot. Here NFPA 10 gives three choices:

  • a vapor-suppressing foam unit (Annex C.2.6.3 says this is often the best choice when only one person will apply agent);
  • several non-vapor-suppressing Class B units applied at the same time from different sides; or
  • a larger unit, 10 lb or more, discharging at 1 lb/sec or more, whose flow can wrap around the object.
Shut the fuel off first. NFPA 10 Annex C repeats the same caution for pressure fires twice: it is undesirable to try to put one out unless there is reasonable assurance that the fuel can be shut off promptly. Kill the flame while fuel is still spraying and you have made a vapor cloud. At a station that means the emergency shutoff button before the pull pin.

The five ways a Class B fire burns

Annex C.2.6 sorts flammable liquid and gas fires into five configurations. Only the first two are what a Class B rating is tested on. The UL test burns heptane at least 2 in. deep in a square pan, which is why a 160-B rating tells you nothing about a spray fire.

ConfigurationWhat it looks likeWhat NFPA 10 asks for
SpillUncontained liquid on a flat surfaceClass B rating and distance per Table 6.3.1.1
Fuel in depthMore than 1/4 in. deep: dip tanks, quench tanks, pansRating by surface area, 50 ft travel (6.3.2)
ObstacleFuel all around a sizable objectFoam, several units at once, or 10 lb+ at 1 lb/sec+ (5.5.3)
Three-dimensionalPouring, running, dripping fuelDry chemical 10 lb+ at 1 lb/sec+ (5.5.2)
PressureForced, pumped or sprayed fuel; gas jetsDry chemical 10 lb+ at 1 lb/sec+ (5.5.1.1)

From NFPA 10 (2018) Annex C.2.6 and Chapter 5. Travel distance for the last three: 30 ft for hand portables, 100 ft for wheeled units of 125 lb or more (6.3.3).

Why the rate matters more than the size

Dry chemical stops a flame by interrupting the chemical chain reaction in the burning vapor. On a still pan you can sweep the cloud across the surface a little at a time; the fuel is not going anywhere. On a pressure or running-fuel fire, new vapor is arriving every second. Annex C.2.6.5 puts it plainly: the nozzle design and the flow rate have to meet or exceed the minimum critical application rate for that fuel. Below that rate, more powder over more time does not add up to an extinguishment; the fire simply eats it.

Manufacturers get the higher rate with bigger valves, siphon tubes, hoses and nozzle orifices. The trade-off is range and duration. Amerex describes its standard “Compliance Flow” models as the choice for long range and the highest UL ratings, and its “Fast Flow” models for flow rate, quick knockdown and more operator protection. Its High Flow line claims about twice the flow rate of standard models. A 10 lb high-flow unit is empty in roughly 9 to 11 seconds, so the operator has to be close, aimed at the base, and ready.

The technique for a pressure fire (NFPA 10 Annex C.2.6.5): inject the powder at roughly 15 to 45 degrees through the source of the fuel and work the flame outward, wiping it off the fuel. For running fuel (C.2.6.4): start at the bottom and work up.

▶ Watch: “Specialty Fire Extinguishers: Performance, Protection and Innovation”

Courtesy of Amerex. Brayden Banks of Amerex explains the difference between high flow and fast flow extinguishers (October 2025). The second part of the video covers Amerex’s HT Series clean agent units, which are not high flow. It’s a manufacturer video, so the products shown are Amerex’s. · Open on YouTube ↑ · @amerexfire939 ↑

Gas stations and fuel islands: NFPA 30A

This is the part Mike McCarthy flagged, and he is right. Until the 2018 edition, NFPA 30A sent stations to NFPA 10’s ordinary Class B tables, which in practice meant a 40-B or 80-B unit somewhere near the pumps. The 2021 edition rewrote the Chapter 9 extinguisher rules to line up with NFPA 10’s pressure-fire selection. NFPA’s own committee statement calls them the “hi-flow requirements instituted for fixed and on-demand fueling.”

WhereExtinguisherPlacement
Motor fuel dispensing (fixed stations, fleet sites)10 lb ABC dry chemical, 1 lb/sec or moreOutdoors: at least one per island or island group, within 75 ft. Indoors: 15–50 ft from the dispenser, on the way out. Up to 100 ft to a 20 lb high-flow unit.
Gaseous fuel dispensing (CNG, LNG)SameAt least one 15–50 ft from each dispenser or group
Repair garagesSameAt least one in every garage; 50 ft max from any point
Marine fueling (2024 edition)20 lb ABC dry chemical, 1 lb/sec or more100 ft max along walkways of the dock or pier; stairs and ladders don’t count
Mobile fueling trucks10 lb ABC dry chemical, 1 lb/sec or moreCarried on the vehicle

Dispensing, gaseous and garage rows: 2021 NFPA 30A text as summarized by Brooks Equipment (sections 9.2.5.2.x in 2021; 9.2.5.3.x in 2024). Marine and mobile rows: NFPA’s A2023 First Revision report (FR-17, FR-36). We have not read the published 2024 book; confirm numbers and distances in the edition your fire marshal enforces.

“Installed, replaced, or exchanged”: why it reaches every station

The 2024 edition says newly installed extinguishers, including replacements or exchanges, must meet the high-flow rule. NFPA’s committee deliberately left out an effective date: adopting a date creates a retroactivity mess when a state adopts the code years later. So nobody gets written up the day the code is adopted for a sound 20 lb standard unit at the island. But that unit will eventually fail a hydrostatic test, get discharged, or get swapped in an exchange program, and its replacement has to be high flow. One service cycle at a time, every station gets there. That is what “going to be mandatory everywhere” means in practice.

For station owners: you do not have to wait for the old units to fail. Swapping them on a service visit you are already paying for closes the question before an inspector or an insurer asks it. If a technician offers a like-for-like replacement at a fuel island, ask whether it meets NFPA 30A’s 1 lb/sec rule.

Which edition applies to you? The rule is in NFPA 30A from 2021 on. A jurisdiction still enforcing an older edition does not have it in the text, and the International Fire Code’s own motor fuel section (§2305.5) sets the extinguisher rating and distance but not a flow rate. Check what your state or local fire code adopts. Even where it is not yet enforceable, the reason behind it is the same fire.

In Georgia, it is enforceable now

Georgia adopts these two documents in two different rules of the State Fire Marshal (Office of the Insurance and Safety Fire Commissioner), which is easy to miss:

  • NFPA 30A, 2024 edition — Rule 120-3-11-.06(2), the ignitable liquids rule (last amended effective May 1, 2025). Georgia’s changes cover attendants, self-service, signs, housekeeping and emergency shutoff breakers. None of them touch the extinguisher section, so the 10 lb, 1 lb/sec rule applies as written. Rule 120-3-3-.04 points to 120-3-11 for NFPA 30A, and Georgia’s IFC amendments replace the IFC’s motor fuel chapter (§2301.1) with the same pointer, so IFC §2305.5 is not what governs a Georgia station.
  • NFPA 10, 2022 edition — Rule 120-3-3-.04(6), with Georgia changes: units of 40 lb or less are mounted with the top no more than 48 in. above the floor (NFPA 10 allows 5 ft); new cabinet openings top out at 50 in.; maintenance and recharging must be done by people licensed or permitted under Title 25, Chapter 12; and tags and collars follow Rule 120-3-23.
  • 2024 IFC and NFPA 101, 2024 edition — also adopted in Rule 120-3-3-.04 (NFPA 101 effective May 27, 2025). The rule was amended five times in 2025, most recently effective December 28, 2025.

Read from the rule text on rules.sos.ga.gov, current through October 21, 2026. Local fire marshals enforce the same state minimums and may add local ordinances.

▶ Watch: “Gas Station Fire Safety - What TFD Inspectors Look For”

Courtesy of Tallahassee Fire Department. A fire inspector walks a gas station: fuel systems, emergency shutoffs, extinguishers, alarms and propane (January 2026). It shows what an inspection covers; it is not specifically about the 1 lb/sec rule. · Open on YouTube ↑ · @TallahasseeFire ↑

How to check a unit: read the data sheet, not the label

The nameplate shows the UL rating, and the rating does not tell you the flow. To check an installed unit:

  1. Read the manufacturer and model number off the nameplate.
  2. Find the manufacturer’s data sheet for that model. Look for a row called discharge rate, average discharge rate, or agent flow rate, in lb/sec.
  3. Confirm it is 1.0 lb/sec or more and the unit holds 10 lb or more of dry chemical (20 lb at a marine fuel dock).
  4. Do not stop at the product name. Amerex’s 13.2 lb ABC and Purple-K units in its “Fast Flow” family average 0.94 lb/sec on its own data sheet.
ModelAgent · sizeUL ratingDischargelb/sec
Amerex 720 High FlowABC · 10 lb1-A:20-B:C10 s1.22
Amerex 722 High FlowPurple-K · 10 lb20-B:C11 s1.15
Amerex 760 High FlowABC · 20 lb4-A:60-B:C19 s1.14
Ansul Sentry HF-AA10SABC · 10 lb1-A:20-B:C9.0 s1.26
Buckeye 11351 Heavy Duty High FlowABC · 10 lb1-A:20-B:C10 s1.11
Ansul Sentry HF-PK10SPurple-K · 10 lb20-B:C8.9 s1.30
Ansul Sentry HF-PK20Purple-K · 20 lb60-B:C18.2 s1.19
Amerex 594 Fast FlowABC · 13.2 lb2-A:40-B:C15 s0.94 ✗
Amerex 589 Compliance FlowABC · 30 lb20-A:160-B:C34 s0.95 ✗

Manufacturer figures from Amerex’s High Flow and High Performance data sheets, Ansul’s Sentry High-Flow listing and Buckeye’s Heavy Duty High Flow spec sheet. Brands shown as examples only; other manufacturers make high-flow units too. Always use the current data sheet for the exact model on the wall.

10 lb or 20 lb? Weight matters

The rule is 10 lb or more, and 10 lb high-flow units are easy to find: Amerex (720, 721, 722), Ansul Sentry (HF-AA10S, HF-PK10S) and Buckeye (11351, 11651, 11851) all make one. A 20 lb unit is a different thing to carry. The number on the label is the powder only; with the steel cylinder, valve and hose, Amerex lists its 10 lb High Flow at 19 lb and its 20 lb High Flow at 39 lb shipping weight, and its 30 lb High Performance units at 58 lb. Grab a 20 lb unit off the wall and you are running with about 40 lb in one hand.

NFPA 10 takes the operator into account. Annex H.1 (2018) says the physical ability of the user should be considered when a unit is selected, and that wheeled units or fixed systems are the answer when the hazard outgrows a hand portable. Section 6.1.3.8 also lowers the mounting: units over 40 lb gross weight (except wheeled) go with the top no more than 3½ ft above the floor, instead of 5 ft. (Georgia goes further: units of 40 lb or less top out at 48 in.) So unless the code asks for 20 lb (a marine fuel dock under NFPA 30A 2024) or you need the 100 ft placement allowance a 20 lb unit buys at a station, a 10 lb high-flow unit is the one most staff can actually use. Pick it, train on it, and add units rather than size.

Stored pressure or cartridge-operated?

Both exist in high-flow versions. Cartridge-operated units (Ansul Red Line is the best-known) keep the expellant gas in a separate cartridge and are used in refining, petrochemical, oil and gas, and mining, where units get knocked around and must work in the cold. Stored-pressure units are cheaper to buy and to service. Either is acceptable if the model is listed and its data sheet shows 1 lb/sec or more.

Where else to look for a pressure fire hazard

  • Generator rooms and fire pump rooms with pressurized diesel supply lines and day-tank pumps.
  • Hydraulic equipment: elevator machine rooms, presses, injection molding, trash compactors.
  • Propane cylinder exchange and filling, forklift fueling, natural gas trains on boilers.
  • Fleet fueling, maintenance shops, paint mixing rooms with pumped solvents.
  • Loading racks, drum dispensing, and anywhere fuel is moved through a hose under pressure.

A pressure hazard is defined by the fuel being forced, pumped or sprayed, not by the occupancy. A hospital generator room can need one as much as a refinery does.

Edition crosswalk

TopicNFPA 10 (2013)NFPA 10 (2018)NFPA 10 (2026)
Pressurized liquids and gas5.5.1.1.2 (and 5.5.1.1.1: follow the manufacturer’s recommendations)5.5.1.15.5.4.1
Three-dimensional5.5.25.5.25.5.4.2
Obstacle5.5.45.5.35.5.4.3
Travel distance6.3.36.3.36.3.3

2013 and 2018 read in the owner’s copies. 2026 from NFPA’s A2025 revision record. The 2022 edition was not read; check its numbering in your copy. The 2013 edition is the one that added the 30 ft / 100 ft travel distances for these hazards. Secondary sources date the 10 lb / 1 lb/sec wording to the 2007 edition; before that, NFPA 10 left the choice to the manufacturer’s recommendations.

Walk-through checklist

  • Is any fuel here forced, pumped, sprayed, pouring or running? If yes, the nearest Class B unit has to be high flow.
  • Is the unit dry chemical, 10 lb or larger (20 lb at a marine fuel dock)?
  • Does the model’s data sheet show 1 lb/sec or more? Note the model number on your report.
  • Is it within 30 ft of the hazard (100 ft for wheeled units of 125 lb or more), or within the NFPA 30A distances at a station?
  • Can the operator reach the emergency fuel shutoff before reaching the fire?
  • At a station: was any extinguisher replaced or exchanged since your jurisdiction adopted NFPA 30A 2021 or later? Each one must be high flow.
  • Are staff trained to aim at the base, start at the bottom on running fuel, and expect a 10-second discharge?

Inspection Report Language

OBSERVATION: The portable fire extinguisher serving the fuel dispensing island (Model ______, 20 lb ABC, rated 20-A:120-B:C) has a manufacturer-published average discharge rate of 0.65 lb/sec. The unit was installed as a replacement after the jurisdiction adopted NFPA 30A (2021 or later). FIELD BASIS: NFPA 30A (2021 and later) requires portable extinguishers installed to comply with the code at motor fuel dispensing facilities, including replacements and exchanges, to be at least 10 lb ABC dry chemical with an agent discharge rate of 1 lb/sec (0.45 kg/sec) or more. NFPA 10 5.5.1.1 (2018) applies the same size and rate to pressurized flammable liquid and gas fire hazards. RISK: A fuel spray or pressure fire at the dispenser can be fed faster than this unit discharges agent. The operator may empty the extinguisher without achieving knockdown while standing close to the fire. RECOMMENDED CORRECTIVE ACTION: Replace with a listed dry chemical extinguisher of 10 lb or more whose manufacturer data sheet shows an average discharge rate of 1 lb/sec or more, located per NFPA 30A and the adopted fire code. Record the model number and discharge rate on the service tag or report. Confirm staff know the location of the emergency fuel shutoff.

Ask Clara

Not sure whether a room has a pressure fire hazard, or whether the unit on the wall meets the 1 lb/sec rule? Clara, the site’s assistant, knows this article and the NFPA 10 hub.

SUGGESTED PROMPT

“We have a fuel island and a generator room with a diesel day tank. Which of our extinguishers need to be high flow, and how do I check the ones we already have?”

Frequently Asked Questions

What is a high-flow fire extinguisher?
A dry chemical extinguisher that discharges its agent at an average of at least 1 lb per second (0.45 kg/sec). NFPA 10 does not use the words "high flow" or "fast flow" — those are manufacturer product names. The requirement itself is a size and a rate: dry chemical, 10 lb or more, discharging at 1 lb/sec or more. Manufacturers build these units with larger valves, siphon tubes, hoses and nozzles so the same powder comes out roughly twice as fast as a standard unit.
Where does NFPA 10 require a high-flow extinguisher?
On three kinds of Class B hazard. Pressurized flammable liquid and gas fires (fuel that is forced, pumped or sprayed), and three-dimensional fires (fuel that is pouring, running or dripping) both require dry chemical extinguishers of 10 lb or more at 1 lb/sec or more — NFPA 10 (2018) 5.5.1.1 and 5.5.2. Obstacle fires (fuel all around a sizable object) allow one of three choices: a vapor-suppressing foam unit, several units applied at the same time, or a 10 lb+ unit at 1 lb/sec+ — 5.5.3. In the 2026 edition these are 5.5.4.1, 5.5.4.2 and 5.5.4.3.
Are high-flow extinguishers required at gas stations?
Under NFPA 30A, yes, from the 2021 edition on. Every portable extinguisher installed to meet the code at a motor fuel dispensing facility must be at least 10 lb ABC dry chemical with a discharge rate of 1 lb/sec or more, and the rule applies to new installations, replacements and exchanges. NFPA deliberately left out an effective date, so a station is not cited for its old units on the day the code is adopted — but each unit that is replaced has to be high flow, which is why the whole market is moving there. Whether it is enforceable at your site depends on which NFPA 30A edition your state or local fire code adopts; ask your fire marshal. In Georgia it is enforceable now: Rule 120-3-11-.06 adopts NFPA 30A, 2024 edition, without changing the extinguisher section.
Is a 20 lb extinguisher automatically high flow?
No. Capacity and flow rate are separate numbers. On Amerex’s own data sheet, a 30 lb ABC unit rated 20-A:160-B:C averages 0.95 lb/sec and a 20 lb ABC rated 20-A:120-B:C averages 0.65 lb/sec — both below the line — while a 10 lb High Flow unit averages 1.22 lb/sec. Big B ratings come from long range and long discharge on a still pan of fuel, which is the opposite of what a pressure fire needs.
How do I tell if an installed extinguisher is high flow?
Not from the UL rating — the label shows the A:B:C rating, and the Class B rating test does not measure performance on pressure or running-fuel fires. Read the model number off the nameplate and look it up on the manufacturer’s data sheet, which lists the average discharge rate in lb/sec. Most high-flow units also say "High Flow" or "Fast Flow" on the label, but a product name is not proof: Amerex sells 13.2 lb "Fast Flow" models that average 0.94 lb/sec.
Does a high-flow extinguisher make it safe to fight a fuel-spray fire?
Only if the fuel can be shut off. NFPA 10 Annex C warns that it is undesirable to try to extinguish a pressure fire unless there is reasonable assurance that the source of fuel can be shut off promptly. Knocking the flame down while fuel keeps spraying creates a vapor cloud that can re-ignite. Hit the emergency shutoff first; the extinguisher is for the flame that is left.
How far can a high-flow extinguisher be from the hazard?
NFPA 10 (2018) 6.3.3 limits actual travel to a pressure, three-dimensional or obstacle fire hazard to 30 ft for hand portables and 100 ft for wheeled units with 125 lb of agent or more, unless another document says otherwise. NFPA 30A sets its own placement for fuel dispensing (for example, one unit per island or island group within 75 ft outdoors, per the 2021 text), so at a station you follow NFPA 30A and your fire code.
FROM SAMEKTRA
Need someone to actually run this inspection on schedule?

We curate a vetted network of approved vendors so you get one relationship instead of chasing five contracts — or let an analyst run your whole compliance calendar automatically, reports audited on arrival.

References

1. NFPA 10, Standard for Portable Fire Extinguishers, 2013 and 2018 editions (read in the owner’s copies): 5.5.1.1, 5.5.2, 5.5.3 (5.5.4 in 2013), 6.3.3, A.5.5.1.1, A.5.5.2, A.5.5.3(2), C.2.6–C.2.8. 2026 numbering from NFPA’s A2025 revision record.

2. NFPA, NFPA 30A A2023 First Revision Report — FR-16 (new installations, replacements and exchanges; no effective date), FR-17 (marine fueling: 20 lb ABC at 1 lb/sec, 100 ft), FR-36 (mobile fueling: 10 lb ABC at 1 lb/sec).

3. NFPA 30A (2024), edition history: Chapter 9 extinguisher requirements revised in the 2021 edition to align with NFPA 10.

4. Brooks Equipment, “New NFPA Requires High-Flow Extinguisher for Fuel Dispensing Areas and Repair Garages” (Feb 2022) — 2021 NFPA 30A section numbers and travel distances.

5. Amerex, High Flow data sheet (models 720/760/721/761/722/762) and High Performance data sheet (Fast Flow and Compliance Flow models).

6. Ansul Sentry High-Flow listing, Fox Valley Fire & Safety (HF-AA10S, HF-PK10S, HF-AA20-1, HF-PK20).

7. Amerex Learning Center, “Fast Flow vs Compliance Flow”; Boraas, “Taking Control with the Right Flow”, Occupational Health & Safety (April 2018).

8. International Fire Code §2305.5, motor fuel-dispensing facilities — portable fire extinguishers. Georgia: Rule 120-3-11-.06 (NFPA 30A, 2024 edition) and Rule 120-3-3-.04 (NFPA 10, 2022 edition, with Georgia modifications; IFC §2301.1 replaced by a pointer to Subject 120-3-11).

9. Buckeye Fire Equipment, Heavy Duty High Flow spec sheet (10, 13.2, 20 and 30 lb models), as published by WebstaurantStore. NFPA 10 (2018) 6.1.3.8 and Annex H.1 on weight and mounting height.

10. Videos: Amerex, “Specialty Fire Extinguishers: Performance, Protection and Innovation” (Oct 2025); Tallahassee Fire Department, “Gas Station Fire Safety - What TFD Inspectors Look For” (Jan 2026).

11. Field contribution: Mike McCarthy, FirePro Inc., Lawrenceville, GA — fireproga.com.