Wet alarm check valve and trim
The riser in most sprinklered buildings: water held behind a check valve, an alarm line that fills when water moves, and a gong that rings with no power.
Water A little water Empty pipeTypical arrangement — trim and parts vary by manufacturer.
PART
Supply pressure gauge
Also called: lower gauge, water supply gauge
The gauge below the clapper. It shows the pressure the water supply delivers to the riser, and it is the gauge read for the static and residual readings in a main drain test.
WHAT THE INSPECTOR CHECKS
- Inspected for condition and a normal reading; replaced or checked against a calibrated gauge, and must read within 3% of full scale. NFPA 25 §13.2.4
HOW OFTEN (NFPA 25, 2023)
| Inspection (water gauge) | quarterly | NFPA 25 §13.2.4 |
| Replace or calibrate | 5 years | NFPA 25 §13.2.4 |
COMMON DEFICIENCY
Needle stuck, face fogged, or no record of replacement or calibration in the last five years. NFPA 25 §13.2.4
Read the article →PARTS IN THIS ASSEMBLY