Skip to main content
🧰 SAMEKTRA SERVICES →
← Fire Protection
FIRE ALARMEMERGENCY LIGHTINGEXIT SIGNSNFPA 72NFPA 101

Batteries in Fire Alarms, Emergency Lights and Exit Signs
When they expire, how often to replace them, and which test decides it

When the power fails, the fire alarm, the emergency lights and the exit signs run on batteries that have been losing capacity since the day they went in. Here is how to check them, and when the codes say to replace them.

By Stanislav Samek, Samektra · 14 min read · Last updated October 20, 2026
Headshot of Stanislav Samek, founder of Samektra Safety Management & Training
WRITTEN BY · FOUNDER & EDITOR

Stanislav Samek

Founder of Samektra Safety Management & Training in Gwinnett County, Georgia, and the writer and editor behind LifeSafetyWiki.

Go look at the date on your batteries

Open the fire alarm panel and look at the two batteries sitting in the bottom of the cabinet. Somewhere on each one there should be a month and a year. Now walk to the nearest emergency light, press its test button, and ask yourself when that battery went in. Then do the same at the exit sign over the stair door.

The fire alarm battery has a date the code requires. Emergency lights and exit signs have a test the code requires, but no date. And all of them fail the same way: not all at once, but a little every month. The light still comes on when you press the button. The panel shows no trouble. Then the power goes out, and the battery that looked fine runs flat long before it should.

The short version. Fire alarm batteries: plan on four years, test twice a year. Emergency lights and battery exit signs: 30 seconds every month, 90 minutes every year, replace what fails. None of them tell you they are getting weak. Only a test does.
What this article covers. Batteries: the standby batteries in the fire alarm panel and its power supplies, and the batteries inside emergency light units and exit signs. Some emergency lights and exit signs have no battery of their own and run from the emergency generator; they are tested with the generator under NFPA 110 (NFPA 101 §7.9.2.4). Buildings with one central battery or inverter test it under NFPA 111. Exit signs that need no power at all, self-luminous and photoluminescent signs, have their own rules. None of those are covered here.

A battery does not die. It fades.

Every rechargeable battery loses capacity as it ages. It still takes a charge, it still shows the right voltage on the charger, and it still lights the lamp when you press the test button. What changes is how long it can keep going. A lead-acid battery is treated as worn out once it can deliver only 80 percent of its rated capacity, which is why the 2022 edition of NFPA 72 sizes fire alarm batteries with a 1.25 aging factor: the battery has to be big enough on its last day, not its first.

That is the trap. A quick test uses a small part of the charge, so a battery that has lost half its capacity still passes it. The only test that finds a tired battery is one that runs it for the full time it has to work in a real outage: 1½ hours for an emergency light, and a load test for a fire alarm panel. Heat makes it worse. Battery makers state that life is roughly halved for every 10 °C (18 °F) above room temperature, so a unit in a hot stair or mechanical room wears out years early.

So the two habits that matter: write the install date on every battery, so you know how old it is, and run the full-length tests, so you know what it can still do.

Fire alarm batteries: the date the code requires

A fire alarm panel must have a secondary power supply that runs the system for 24 hours in normal standby and then 5 minutes in full alarm (NFPA 72 §10.6.7.2.1). In almost every building that supply is a pair of 12-volt sealed lead-acid batteries in series, the same valve-regulated (VRLA) type used in alarm power supplies, annunciators and booster panels.

The date marking

Every storage battery is marked with the month and year of manufacture. If the manufacturer did not mark it, the installer finds the date code and writes it on (§10.6.10.1). That date is the starting point for everything else, and a battery with no readable date is a finding on its own.

A fire alarm power supply with its door open. The two 12 V standby batteries in the bottom of the cabinet are not a matched pair: one is a 7 Ah sealed lead-acid battery, the other a different make, and neither shows an installation date or a current test date. Nobody could say how old they were, when they were last tested, or when they are due. Batteries in a series string are replaced together, same size and same date. Field photo from an environment-of-care round.

The 2022 edition goes one step further. The installer also labels each battery with a replacement date no more than 4 years after installation, and from January 1, 2024 rechargeable batteries must be listed or recognized by a testing laboratory. The committee’s reason for the four years was simple: that is the replacement cycle the battery manufacturers recommend. The 2022 edition also changed the battery calculation, replacing the old 20 percent margin with a 1.25 aging factor, because a lead-acid battery is at end of life once it drops to 80 percent of its rated capacity.

The tests, and why the edition matters

Which test schedule applies depends on which edition your building is held to. That is not a small detail: in Georgia the fire marshal enforces NFPA 72-2022, while CMS and The Joint Commission hold hospitals to NFPA 72-2010 through NFPA 101-2012.

2010 and 2013 editions (CMS for healthcare)
  • Visual inspection of sealed lead-acid batteries every six months: corrosion, leaks, tight connections, and the month/year marking (Table 14.3.1).
  • Once a year: a charger test, a discharge test under the full alarm load, and replacement if the recharged voltage or current falls below the manufacturer’s figure (Table 14.4.3.2).
  • Every six months: a load voltage test.
2019 and 2022 editions (Georgia fire marshal)

Only VRLA and primary (dry cell) batteries remain in the tables. VRLA batteries get a sequence of tests every six months:

  1. Temperature. Infrared reading at the negative terminal. Replace if the battery is more than 18 °F (10 °C) warmer than the inside of the cabinet.
  2. Charger. Output within the manufacturer’s limits.
  3. Voltage. Replace any unit reading below 13.26 volts while fully charged on the charger.
  4. Ohmic test. Compare with the baseline recorded at installation. Replace at a 30 percent change in conductance or a 40 percent change in resistance or impedance. A load test may be done instead.
  5. Every 3 years: replace the batteries, or load test them; replace at 80 percent capacity or less.

A panel that load tests its own batteries and records the cabinet temperature may stand in for the manual tests.

Two clocks, one battery. In the 2022 edition the replacement label (Chapter 10) says four years from installation, while the test table (Chapter 14) allows a three-year load test as the alternative to replacement. Read them together: the label is the latest a battery may stay in service, and the tests can retire it sooner. Most service companies simply replace on a four-year cycle, or sooner, and record the dates on the inspection report.

▶ Watch: load testing fire alarm batteries

Courtesy of GB Fire Pro (about 5 minutes). A technician load tests the batteries in a fire alarm panel and checks the charging voltage. The panel in the video had failed its batteries two years in a row because the charger was never turned on in the program after the panel was replaced, so the batteries sat there without a charge. The batteries looked fine. The test is what found it. · Open on YouTube ↗

What shortens battery life

  • Heat. Battery makers state that life is roughly halved for every 10 °C (18 °F) above normal room temperature. A panel in a hot mechanical room or an attic will not see four years.
  • Deep discharge. A long power outage that runs the batteries flat, or a charger fault, does permanent damage. Test after any long outage.
  • Shelf time. A sealed lead-acid battery loses a few percent of its charge every month in storage. A spare that sat on a shelf for two years is not a new battery. Check the date before you install it.
  • Mismatched pairs. Replace both batteries in a series string together, with the same size and date. Why that matters is below.

Why a mismatched pair is a problem

A fire alarm panel runs on 24 volts, so its two 12-volt batteries are wired in series. The same current runs through both, in and out. That only works when the two are alike. If one is smaller, older or a different make, it empties first during an outage while the other still has charge, and the panel’s run time drops to whatever the weaker battery can give. On the charger it goes the other way: one battery fills before the other, so one ends up overcharged while its partner stays undercharged, and both age faster. Power-Sonic’s technical manual is blunt about it: do not mix batteries of different capacities, ages or makes in a series string.

Is there a code for it? Not a sentence that says “matched pair”. But NFPA 72 requires system components to be installed, tested and maintained according to the manufacturer’s published instructions (§10.3.2 in the 2013 edition), and the battery maker’s instructions say not to mix them. The panel was also sized for a battery of a stated type and capacity in its battery calculation; a smaller or tired battery in the string means that calculation no longer holds. And the 2022 edition requires rechargeable batteries installed from 2024 on to be listed or recognized. A mixed pair is a finding. Replace both, same type, same capacity, same date.

▶ Watch: changing the batteries in a fire alarm panel

Courtesy of The Fire Alarm Expert (about 4 minutes). How a fire alarm technician swaps the standby batteries in a panel. Replace both at once, and write the date on each new battery before you close the door. · Open on YouTube ↗

Swelling, cracked cases, leaking and corroded terminals mean replace now. You do not need a meter to see any of them. More on sizing and load testing is in Fire Alarm Batteries & Standby Power.

Emergency lights: the test the code requires, not a date

The Life Safety Code does not put a date on emergency light batteries. It puts a test on them instead, and the test is what retires a battery (NFPA 101 §7.9.3):

  • Monthly: a functional test of at least 30 seconds, with tests 3 to 5 weeks apart.
  • Yearly: a test of at least 1½ hours for battery-powered units. The light must stay lit for the whole test.
  • Records: written, kept by the owner, available to the AHJ.

The 90-minute test is the one that finds tired batteries. A battery that can light a lamp for 30 seconds may die at minute 40. That is why the annual test has to be run for the full duration, with someone walking the building at the end to see which units are still lit.

▶ Watch: how often the Life Safety Code wants emergency lighting tested

Courtesy of NFPA LiNK (about 3 minutes). NFPA’s own explanation of the emergency lighting test frequencies in the Life Safety Code. Check which edition your building is held to; CMS uses the 2012 edition. · Open on YouTube ↗

Self-testing units

For existing battery lights the 2012 edition adds one more line: they must use reliable rechargeable batteries with a way of keeping them properly charged (§7.9.2.6). A unit whose charger has failed is running down every day, even though nothing looks wrong.

Self-testing or self-diagnostic units run the monthly test on their own and show a fault light when they fail. Under the 2012 edition staff still look at them every 30 days and the annual 1½-hour test is still done and written down (§7.9.3.1.2), even on units that run a 90-minute test of their own. Only computer-based systems that run the test and keep a test and failure history take the annual test over (§7.9.3.1.3). Read the product sheet before you count on the unit for the annual test: one widely used self-testing exit sign runs a 1-minute test every 30 days and a 30-minute test at 6 and 12 months. That is not a 90-minute test.

How long the batteries last

It depends on the chemistry, and the figures come from manufacturers, not from the code. Sealed lead-calcium packs are commonly sold with warranties of one to three years; nickel-cadmium units are often rated around 10 years of service life. A warranty is not a service life, so write the install date on every replacement battery and let the annual test tell you when it is done.

Exit signs with a battery

An exit sign with a battery is tested the same way as the emergency lights: 30 seconds monthly, 1½ hours yearly (NFPA 101 §7.10.9). The 2012 edition also requires the light sources of every exit sign to be looked at at least every 30 days. The 2024 edition dropped that separate sentence, but CMS still enforces 2012, so in a hospital the 30-day check stays.

The monthly test in practice: press and hold the test button and the sign should stay lit on its battery. This weatherproof sign over a parking deck stair door failed. The battery could no longer carry it, and in a power cut that stair would have lost its exit sign. Field photo from an environment-of-care round.

An LED exit sign almost never needs a new lamp, so it is easy to forget it has a battery at all. It does, and it ages exactly like the battery in an emergency light. The sign looks perfect every day until the day it has to run on its own.

How to test them properly

Press the button once, the light comes on, done? No. That only proves the bulb and the switch work. The battery has not been asked to do anything yet. Here is how the monthly and annual tests are meant to be done, on the units most buildings have.

Units with a plain test button

  • Hold it, do not tap it. On a unit with no self-test, the light stays on only while you hold the button and goes off when you let go (Lithonia ELM2 instructions). The monthly test is at least 30 seconds (NFPA 101 §7.9.3.1.1), so count it out.
  • Watch the whole 30 seconds. The lamps must stay fully lit for the entire test. A unit that starts bright and fades, or goes out at 20 seconds, has failed.
  • Space the tests 3 to 5 weeks apart, and write down the date, the unit, the result and who did it.
  • The annual test is 1½ hours, which nobody does with a finger on a button. The usual way is to switch off the normal power to the units for the full time, then walk the building at the end and see which ones are still lit. Plan where people will be first: the area has little or no emergency lighting for up to a day while the batteries recharge.

▶ Watch: a technician’s exit and emergency light check

Courtesy of Koorsen Fire & Security (about 3 minutes). A fire protection company’s technician shows the quick check done on exit signs and emergency lights to make sure they will run when the power fails. · Open on YouTube ↗

Self-testing units: the button does different things

On self-testing units one press usually starts a short timed test, and you do not have to hold it. The way to start the longer tests is not the same from one maker to the next. These come from each maker’s own instruction sheet:

Unit1 press2 presses3 pressesNotes
Lithonia ELM2 (no self-test)Light stays on only while you hold the button——Charge 24 h before the first test
Lithonia ELM2L with SDRT self-test30-second test (same press cancels)No manual 90-minute sequence—Runs 5 min monthly and 90 min yearly on its own
Compass self-diagnostic (Current / Dual-Lite)30 seconds15 minutes90 minutesPresses within 2 seconds
Compass CUSO self-test option1 minute5 minutes30 minutes4 presses within 2 seconds: 90 minutes
Dual-Lite EVE / EVE4X exit sign1 minute90 minutes—Spectron self-diagnostics
Sure-Lites SELA30 secondsPress again during the 30 s test: 90 minutes—Press during the 90-minute test to cancel
CDE Series edge-lit exit sign30 seconds30 minutes90 minutesHold 3–5 s: interruption; over 6 s: reset
“Press it five times for the 90-minute test.” We could not find a manufacturer that says this. Two, three or four quick presses, or a second press during the short test, are the sequences we found, and they change from model to model even within one brand. Some units have no manual 90-minute test at all. On the Dual-Lite EVE sign and the Compass CUSO option, five red blinks is a fault code (emergency lamp fault), not a test. Find the instruction sheet for your model; the model number is on the label inside the unit.

▶ Watch: automatic versus manual testing

Courtesy of Acuity (about 2½ minutes). A manufacturer video, and it says so: it shows equipment that runs the monthly and the 90-minute annual tests on its own. Useful for seeing what self-testing does. Under the 2012 Life Safety Code a stand-alone self-testing unit still gets the monthly look and the annual test written down; only computer-based systems that keep a test history take the annual test over. · Open on YouTube ↗

Before and after the test

  • Let it charge first. Most of the makers above ask for 24 hours on normal power after installation, and after a power failure, before a test counts (Dual-Lite says several hours). A 90-minute test run the morning after an outage can fail a good battery.
  • Let it recharge after. After the 90-minute test the battery needs time to come back (Sure-Lites asks for 24 hours). Do not run the annual test the day before a storm or a survey.
  • Learn the status light. Each maker has its own code. On the Lithonia SDRT option solid green means charged, one red flash a battery failure, two a lamp failure and three a charger failure; on Compass units two red blinks mean battery failure. A red light is a failed test even if nobody pressed the button.
  • Exit signs follow the same rules. A battery exit sign is tested like an emergency light, monthly and yearly (§7.10.9), and self-testing exit signs use press sequences like the ones in the table. Check the sheet for yours.

In a hospital: what the surveyor writes

  • K-0291 — emergency lighting, including the monthly and annual tests (NFPA 101-2012 §7.9).
  • K-0293 — exit signs (§7.10).
  • K-0345 — fire alarm testing and maintenance under NFPA 72, which is where missing or failed battery tests are written up.

Since January 2026 The Joint Commission files these under the Physical Environment chapter: emergency lighting and exit sign testing under PE.03.01.01 EP 3 and PE.04.01.01 EP 1, fire alarm testing under PE.04.01.01 EP 2. The record needs the activity, the date, the inventory, the frequency, who did it, the NFPA standard and the result. A test that was done but not written down is a test that did not happen.

The battery calendar

BatteryDate on itTestsReplace
Fire alarm panel and power supply batteries (VRLA / sealed lead-acid)Month and year of manufacture on every battery. 2022: a replacement date no more than 4 years after installation.Semiannual temperature, charger, voltage and ohmic tests (2019/2022); replace or load test every 3 years.Plan on 4 years. Replace sooner on any failed test, swelling, leaking or heat.
Emergency light unitsNot set by NFPA 101. Write the install date on the battery.Monthly 30-second test; annual 1½-hour test (NFPA 101 §7.9.3).When a test fails. Chemistry decides the life: lead-calcium a few years, nickel-cadmium about 10 (manufacturer figures).
Battery exit signsSame as emergency lights.Tested with the emergency lights (§7.10.9). 2012 edition: light sources looked at every 30 days.When a test fails.

Check the edition your AHJ enforces before you write a finding. The fire alarm rows above follow NFPA 72-2019/2022; for CMS surveys use the 2010 table.

Writing it up

OBSERVATION: The two 12 V, 7 Ah standby batteries in the main fire alarm control unit carry no month/year marking and no installation or replacement date. No load test or ohmic test result was found in the last two semiannual inspection reports. FIELD BASIS: NFPA 72 requires storage batteries to be marked with the month and year of manufacture (§10.6.10.1) and tested at the frequencies in Table 14.4.3.2. The 2022 edition also requires a replacement date no more than 4 years after installation. RISK: Without a date or test history there is no way to show the secondary supply can run the system for 24 hours and then 5 minutes in alarm during a power failure. RECOMMENDED CORRECTIVE ACTION: Replace both batteries with listed batteries of the size in the battery calculation, mark the month/year and the replacement date on each, record a baseline ohmic reading, and add the battery tests to the semiannual inspection scope.

SUGGESTED PROMPT

“Which battery tests and replacement intervals apply to my fire alarm panel, emergency lights and exit signs, and how do they differ between NFPA 72-2010 (CMS) and NFPA 72-2022?”

Frequently Asked Questions

How often should fire alarm batteries be replaced?
NFPA 72 does not give one fixed interval in every edition. The 2022 edition requires the installer to label each battery with a replacement date no more than 4 years after installation, which matches the battery makers’ recommended cycle. Separately, the 2019 and 2022 test tables call for semiannual temperature, charger, voltage and ohmic tests and a replace-or-load-test every 3 years. Any battery that fails a test, swells, leaks or runs hot is replaced at once.
Does NFPA 72 require a date on fire alarm batteries?
Yes. Batteries are marked with the month and year of manufacture; if the manufacturer did not mark them, the installer does (NFPA 72-2013 §10.6.10.1; the same rule is in the 2022 edition at §10.6.10.1). The 2022 edition adds a replacement-date label.
How often are emergency lights and exit signs tested?
NFPA 101 §7.9.3: a functional test of at least 30 seconds every month (3 to 5 weeks apart) and a 1½-hour test once a year for battery-powered units, with written records. Self-testing units run the monthly test themselves, but staff still check them and the annual 1½-hour test is still required.
Why does a battery pass the monthly test and fail the annual one?
Because a rechargeable battery loses capacity as it ages. It still charges and the light still comes on, it just holds less. A 30-second test uses a small part of the charge, so a worn battery passes it. Only the full 1½-hour test shows how much is left, which is why the code requires it once a year for battery-powered units.
Is it a code violation to mix two different batteries in a fire alarm panel?
No code sentence says "matched pair", but NFPA 72 requires equipment to be installed, tested and maintained according to the manufacturer’s published instructions (§10.3.2 in the 2013 edition), and battery makers tell you not to mix batteries of different capacity, age or make in a series string. A mixed pair also no longer matches the battery calculation the panel was sized for. Replace both, same type, same date.
How do I start a 90-minute test on a self-testing emergency light?
It depends on the make, so read the instruction sheet. Common sequences are two presses (Dual-Lite EVE exit signs), three quick presses (Compass self-diagnostic and CDE units), four quick presses (the Compass CUSO option), or a second press during the 30-second test (Sure-Lites SELA). Even one brand can differ from model to model. Some units, such as the Lithonia SDRT option, have no manual 90-minute sequence and run the yearly test on their own.
Do emergency lights fed by the generator need a battery test?
A fixture that runs only from the emergency generator has no battery of its own. It is tested with the generator under NFPA 110 (NFPA 101 §7.9.2.4), which this article does not cover. A fixture with its own battery is tested under §7.9.3 like any other battery unit.
Which CMS K-tags cover these batteries?
K-291 covers emergency lighting (including its testing), K-293 exit signs, and K-345 fire alarm testing and maintenance, which is where fire alarm battery tests are written up. CMS uses NFPA 101-2012 and the NFPA 72-2010 test table.
FROM SAMEKTRA
Need someone to actually run this inspection on schedule?

We curate a vetted network of approved vendors so you get one relationship instead of chasing five contracts — or let an analyst run your whole compliance calendar automatically, reports audited on arrival.

References

1. NFPA 72, National Fire Alarm and Signaling Code, 2013 ed., §10.6.10 (storage batteries), Table 14.3.1 item 9, Table 14.4.3.2 item 9, §14.4.7.

2. NFPA 72 Technical Committees, A2021 cycle: SIG-FUN First Revision draft (FR-5185 replacement-date label, FR-5147 listed batteries, 1.25 aging factor) and SIG-TMS First Revision statements (VRLA test sequence). FUN draft ↗ · TMS statements ↗

3. NFPA 101, Life Safety Code, 2012 and 2024 eds., §7.9.2.4–7.9.2.6, §7.9.3, §7.10.4, §7.10.9.

4. CMS Form 2786R, Fire Safety Survey Report (K-0291, K-0293, K-0345, K-0918).

5. The Joint Commission, Hospital Accreditation Survey Process Guide 2026, document list (PE.03.01.01 EP 3, PE.04.01.01 EP 1 and EP 2; NFPA 111-2010 §8.4).

6. Power-Sonic, Technical Manual — sealed lead-acid batteries (design life, temperature, self-discharge). PDF ↗

7. Chloride 60 Series exit sign specification sheet (Ni-Cd battery life, self-test schedule). PDF ↗

8. Lithonia Lighting, ELM2 LED installation instructions, EMCSA00764 Rev. H (2017), and ELM2L with SDRT self-diagnostics, 912-00026-004 Rev. B (2018). ELM2 ↗ · ELM2L SDRT ↗

9. Compass (Current Lighting), Self-Diagnostic Test Instructions, SD_INSTR R01 (2022). PDF ↗

10. Dual-Lite (Hubbell), EVE / EVE4X exit sign instructions, 93075008 B (2017). PDF ↗

11. Sure-Lites (Cooper Lighting Solutions), SELA instruction sheet, IB505063EN (2020). PDF ↗

12. CDE Series edge-lit exit sign installation instructions. PDF ↗

13. Minnesota Department of Health, Battery-operated emergency lighting guide (NFPA 101-2012 §7.9.3.1.1–7.9.3.1.3), rev. June 2024. PDF ↗

14. Compass (Current Lighting), CUSO self-diagnostics / self-testing option instructions, COM_CUSO_SD R01 (2022). PDF ↗

Videos: GB Fire Pro, “How to Properly Test Fire Alarm Batteries”; The Fire Alarm Expert, “How To Properly Change Batteries in A Fire Alarm Panel”; NFPA LiNK, “How Often to Test Your Emergency Lighting”; Koorsen Fire & Security, “Day in the Life of a Tech – Exit / Emergency Light Quick Check”; Acuity, “STAR: Automated vs Manual Testing for Emergency Lighting”.

DISCUSSION
Be the first to contribute.

Open the discussion panel to comment, flag an inaccuracy, add field experience, or ask a question. Approved contributions earn SRP and may be incorporated into the article.