Stairwell pressurization test checkoff

Stairwell Pressurization Testing — employer practical training and certification record

The person below completed the Stairwell Pressurization Testing study course on LifeSafetyWiki. It covers general knowledge only. If you use it as part of your training program, test one stair together with building staff running the system, cover Parts 1 and 2, then sign Part 3.

Part 1 — Your site (filled in by the employer)

Building name and addressAs it appears on the test report
Stair tested and system typee.g. Stair B, dedicated, single injection with relief damper
Acceptance criteria usedDesign pressure range and door force limit, from the approved design or employer
Instruments used and calibration datesManometer, door force gauge, thermometer, hygrometer

Part 2 — Hands-on check (by the supervisor or certified air balancing technician)

The employee showed they canOKNot yet
Confirm building staff activated the system in the mode under test, and record the mode and running conditionsICB Stairwell Endorsement job task 3☐☐
Record outdoor and indoor temperature, humidity and wind before testingNFPA 92 (2021) 8.4.6☐☐
Measure the pressure across every stair door with all doors closed, without holding a door open on the tubingNFPA 92 (2021) 8.4.6.1☐☐
Measure the force to open every stair door at the latch side and compare it with the limitNFPA 92 (2021) 8.4.6.2 · NFPA 101 (2021) 7.2.1.4.5☐☐
Compare each reading with the criteria, list every failure, and hand the report to the employerICB Stairwell Endorsement job tasks 4 and 5☐☐

Part 3 — Certification

I certify that the person named above tested a stairwell pressurization system with me, measured pressure differences and door forces correctly, and reported the results against the acceptance criteria.

Keep the signed checkoff with the test report. This form does not replace the employer’s own program, and LifeSafetyWiki does not certify competence. Not an OSHA Outreach (10/30-hour) card.